Apparatus control
ABB Network Partner AB
1MRK 580 150-XEN
Page 6 - 93
Version 1.0-00
SBxx-AU_OP_P Automatic operation is permitted, i.e. the
operator place selector is not in Local posi-
tion, the apparatus is not reserved, not man-
ual selected or not blocked (neither
operation nor update of position). The inter-
locking conditions are not considered
SBxx-BLK_AR Output is activated when reservation is
made. It is used to block autoreclosing
when an operation is in progress
Table 18: Output signals for SWICONB
OUT: DESCRIPTION: