The connection type for the main and the pilot fuse groups must be
consistent.
The settings Vdif Main block, Vdif Pilot alarm and VSealIn are in percentage of the
base voltage, VBase. Set VBase to the primary rated phase-to-phase voltage of the
potential voltage transformer. VBase
is available in the Global Base Value groups; the
particular Global Base Value group, that is used by VDSPVC (60), is set by the setting
parameter GlobalBaseSel.
The settings Vdif Main block and Vdif Pilot alarm should be set low (approximately
30% of VBase) so that they are sensitive to the fault on the voltage measurement
circuit, since the voltage on both sides are equal in the healthy condition. If V
SetPrim
is
the desired pick up primary phase-to-phase voltage of measured fuse group, the setting
of Vdif Main block and Vdif Pilot alarm will be given according to equation
114.
Vdif Main block or Vdif Pilot alarm=
SetPrim
Base
V
V
â‹…100
ANSI13000279 V1 EN-US (Equation 114)
V
SetPrim
is defined as phase to neutral or phase to phase voltage dependent of the
selected ConTypeMain
and ConTypePilot. If ConTypeMain and ConTypePilot are set to
Ph-N than the function performs internally the rescaling of V
SetPrim
.
When SealIn is set to On and the fuse failure has last for more than 5 seconds, the
blocked protection functions will remain blocked until normal voltage conditions are
restored above the VSealIn setting. The fuse failure outputs are deactivated when the
normal voltage conditions are restored.
1MRK 511 401-UUS A Section 13
Secondary system supervision
Bay control REC670 2.2 ANSI 301
Application manual

Table of Contents

Other manuals for ABB rec670

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB rec670 and is the answer not in the manual?

ABB rec670 Specifications

General IconGeneral
BrandABB
Modelrec670
CategoryControl Unit
LanguageEnglish

Related product manuals