Description HR/IR address
(.bit)
DI/Coil bit
address
Writeable Value range Comment
Number of AR shots (shot 1) initiated
by the pickup or trip signal from
element 51N
821 0...255 Counter
Number of AR shots (shot 2) initiated
by the trip signal from element 50P-1
822 0...255 Counter
Number of AR shots (shot 2) initiated
by the digital input signal
823 0...255 Counter
Number of AR shots (shot 2) initiated
by the pickup or trip signal from
element 51P
824 0...255 Counter
Number of AR shots (shot 2) initiated
by the pickup or trip signal from
element 51N
825 0...255 Counter
Number of AR shots (shot 3) initiated
by the trip signal from element 50P-1
826 0...255 Counter
Number of AR shots (shot 3) initiated
by the digital input signal
827 0...255 Counter
Number of AR shots (shot 3) initiated
by the pickup or trip signal from
element 51P
828 0...255 Counter
Number of AR shots (shot 3) initiated
by the pickup or trip signal from
element 51N
829 0...255 Counter
Table 5.1.15.1.-13 Mapping of Modbus data: control points
Description HR/IR address
(.bit)
DI/Coil bit
address
Writeable Value range Comment
LED reset 501 W 1 1 = LED reset
a)
a)
Coil area, only writeable.
Structure 1
The status registers contain information on unread fault and event records, and relay
status. The registers are arranged as in Fig. 5.1.15.1.-2 below.
401
402
403
15 8 7 0
Reserved
Warning code
IRF code
Reserved
FR
ER
SP MP
A040333
Fig. 5.1.15.1.-2 Status registers
When the value of the FR/ER bit is 1, there is one or several unread fault/event
records. If time synchronization is realized via a digital input, either the SP (second-
pulse) or MP (minute-pulse) bit will be activated.
Refer to Table 5.1.18.-1 for IRF codes and Table 5.1.18.-2 for warning codes.
100
REF610REF610
Feeder Protection Relay
Technical Reference Manual - ANSI Version
1MRS755535