Table 5.1.17.-6 Disturbance re corder internal triggering and storing
Event Weighting
factor
Default value of
triggering
mask, V236
Default value
of triggering
edge, V237
a)
Default value of
storing mask,
V238
Pickup of element
51P
1001
Trip of element 51P 2101
Pickup of element
50P
4001
Trip of element 50P 8101
Pickup of element
50P-2
16000
Trip of element 50P-2 32 1 0 1
Pickup of element
51N
64001
Trip of element 51N 128 1 0 1
Pickup of element
50N
256 0 0 0
Trip of element 50N 512 1 0 1
Pickup of element 46 1024 0 0 0
Trip of element 46 2048 0 0 0
Alarm of element 49 4096 0 0 0
Trip of element 49 8192 0 0 0
Σ 682 0 751
a)
0 = rising edge; 1 = falling edge.
Table 5.1.17.-7 Disturbance re corder external triggering and storing
Event Weighting factor Default value of
triggering mask,
V241
Default value of
triggering edge,
V242
a)
Default value of
storing mask,
V243
DI11000
DI22000
DI34000
DI48000
DI5 16 0 0 0
Σ 000
a)
0 = rising edge; 1 = falling edge.
Table 5.1.17.-8 Control parameters
Description Parameter R, W, P Value
Reading of the event buffer L R Time, channel number and event code
Re-reading of the event buffer B R Time, channel number and event code
Reading of relay state data C R 0 = Normal state
1 = The relay has been subject to an
automatic reset
2 = Overflow of the event buffer
3 = Both 1 and 2