Table 5.1.15.1.-7 Mapping of Modbus data: analog data
Description HR/IR address
(.bit)
DI/Coil bit
address
Writeable Value range Comment
Phase current I
a
xI
n
(CT) 404 0...5000 0...50 x FLA
Phase current I
b
xI
n
(CT) 405 0...5000 0...50 x FLA
Phase current I
c
xI
n
(CT) 406 0...5000 0...50 x FLA
Ground-fault current x I
n
(CT) 407 0...20000 0...2000% I
n
(CT)
Phase unbalance 408 0...100 0...100%
Table 5.1.15.1.-8 Mapping of Modbus data: digital data
Description HR/IR address (.bit) DI/Coil bit
address
Writeable Value
range
Comment
Pickup signal from element 51P 409.00 1 0/1 1 = activated
Pickup signal from element 51P CD 409.01 2
Trip signal from element 51P 409.02 3 0/1 1 = activated
Trip signal from element 51P CD 409.03 4
Pickup signal from element 50P-1 409.04 5 0/1 1 = activated
Pickup signal from element 50P-1 CD 409.05 6
Trip signal from element 50P-1 409.06 7 0/1 1 = activated
Trip signal from element 50P-1 CD 409.07 8
Pickup signal from element 50P-2 409.08 9 0/1 1 = activated
Pickup signal from element 50P-2 CD 409.09 10
Trip signal from element 50P-2 409.10 11 0/1 1 = activated
Trip signal from element 50P-2 CD 409.11 12
Pickup signal from element 51N 409.12 13 0/1 1 = activated
Pickup signal from element 51N CD 409.13 14
Trip signal from element 51N 409.14 15 0/1 1 = activated
Trip signal from element 51N CD 409.15 16
Pickup signal from element 50N 410.00 17 0/1 1 = activated
Pickup signal from element 50N CD 410.01 18
Trip signal from element 50N 410.02 19 0/1 1 = activated
Trip signal from element 50N CD 410.03 20
Pickup signal from element 46 410.04 21 0/1 1 = activated
Pickup signal from element 46 CD 410.05 22
Trip signal from element 46 410.06 23 0/1 1 = activated
Trip signal from element 46 CD 410.07 24
Pickup signal from element 49 410.08 25 0/1 1 = activated
Pickup signal from element 49 CD 410.09 26
Alarm signal from element 49 410.10 27 0/1 1 = activated
Alarm signal from element 49 CD 410.11 28
Trip signal from element 49 410.12 29 0/1 1 = activated
Trip signal from element 49 CD 410.13 30
Trip signal from element ARC (light and
current)
410.14 31 0/1 1 = activated
96
REF610REF610
Feeder Protection Relay
Technical Reference Manual - ANSI Version
1MRS755535