129
Parameters O41...O49 and O51 control the physical output contacts
which can be connected to circuit breakers, for instance.
Parameters for IEC 60870-5-103 remote communication protocol
Table 5.1.17.-12 Settings
Description Parameter
(channel 507)
R, W, P Value
Unit address of the relay 507V200 R, W 1...254
Data transfer rate (IEC 60870-5-
103), kbps
507V201 R, W (P) 9.6/4.8
Parameters for Modbus remote communication protocol
Table 5.1.17.-13 Settings
Description Parameter
(channel 504)
R, W, P Value
User-defined register 1 504V1 R, W 0...65535
a)
User-defined register 2 504V2 R, W 0...65535
a)
User-defined register 3 504V3 R, W 0...65535
a)
User-defined register 4 504V4 R, W 0...65535
a)
User-defined register 5 504V5 R, W 0...65535
a)
User-defined register 6 504V6 R, W 0...65535
a)
User-defined register 7 504V7 R, W 0...65535
a)
User-defined register 8 504V8 R, W 0...65535
a)
User-defined register 9 504V9 R, W 0...65535
a)
User-defined register 10 504V10 R, W 0...65535
a)
User-defined register 11 504V11 R, W 0...65535
a)
User-defined register 12 504V12 R, W 0...65535
a)
User-defined register 13 504V13 R, W 0...65535
a)
User-defined register 14 504V14 R, W 0...65535
a)
User-defined register 15 504V15 R, W 0...65535
a)
User-defined register 16 504V16 R, W 0...65535
a)
Unit address of the relay 504V200 R, W 1...254
Data transfer rate (Modbus),
kbps
504V201 R, W 9.6/4.8/2.4/1.2/0.3
Modbus link parity 504V220 R, W 0 = even
1 = odd
2 = no parity
CRC order of Modbus RTU link 504V221 R, W 0 = low/high
1 = high/low
a)
The default value is 0.
Feeder Protection Relay
Technical Reference Manual - ANSI Version
REF610REF610
1MRS755535