167
8. Check lists
Table 8.-1 Setting group 1
Variable Group/
Channel
1 (R, W,
P)
Setting
range
Default
setting
Custo-
mer ’s
setting
Pickup value of element 51P 1S1 0.30...5.0 x I
n
(CT)
0.30 x I
n
(CT)
Operate time of element 51P (51P TDLY) 1S2 0.05...300 s 0.05 s
Time/current characteristic for element 51P 1S3 0...9 0
Time multiplier 51P TD IEC 1S4 0.05...1.00 0.05
Time multiplier 51P TD ANSI 1S5 1.0...15.0 1.0
Resetting time of element 51P (51P RSET) 1S6 0.05...2.50 s 0.05 s
Pickup value of element 50P-1 1S7 0.50...35.0 x
I
n
(CT)
0.50 x I
n
(CT)
Operate time of element 50P-1 (50P-1 TDLY) 1S8 0.04...300 s 0.04 s
Pickup value of element 50P-2 1S9 0.50...35.0 x
I
n
(CT)
0.50 x I
n
(CT)
Operate time of element 50P-2 (50P-2 TDLY) 1S10 0.04...30.0 s 0.04 s
Pickup value of element 51N 1S11 1.0...100% I
n
(CT)
1.0% I
n
(CT)
Operate time of element 51N (51N TDLY) 1S12 0.05...300 s 0.05 s
Time/current characteristic for element 51N 1S13 0...9 0
Time multiplier 51N TD IEC 1S14 0.05...1.00 0.05
Time multiplier 51N TD ANSI 1S15 1.0…15.0 1.0
Resetting time of element 51N (51N RSET) 1S16 0.05...2.50 s 0.05 s
Pickup value of element 50N 1S17 5.0...800% I
n
(CT)
5.0% I
n
(CT)
Operate time of element 50N (50N TDLY) 1S18 0.05...300 s 0.05 s
Pickup value of element 46 1S19 10...100% 100 %
Operate time of element 46 (46TDLY) 1S20 1...300 s 60 s
Full load current 1S21 0.30...1.50 x
I
n
(CT)
0.30 x I
n
(CT)
Time constant of element 49 1S22 1...200 min 1 min
Alarm level of element 49 1S23 50...100% 49
trip
95% 49
trip
Operate time of CBFAIL (Trip Fail) 1S24 0.10...60.0 s 0.10 s
Number of AR shots 1S25 0 = AR is not
in use
1 = shot 1
2 = shot 1
and 2
3 = shot 1, 2
and 3
0
Current limit Arc50P of element ARC 1S26 0.50...35.0 x
I
n
(CT)
2.50 x I
n
(CT)
Current limit Arc51N of element ARC 1S27 5.0...800% I
n
(CT)
20% I
n
(CT)
Checksum, SGF 1 1S61 0...255 0
Feeder Protection Relay
Technical Reference Manual - ANSI Version
REF610REF610
1MRS755535