Variable Group/
Channel
1 (R, W,
P)
Setting
range
Default
setting
Custo-
mer ’s
setting
Checksum, SGF 2 1S62 0...127 0
Checksum, SGF 3 1S63 0...127 120
Checksum, SGF 4 1S64 0...63 0
Checksum, SGF 5 1S65 0...255 0
Checksum, SGB 1 1S71 0...1048575 0
Checksum, SGB 2 1S72 0...1048575 0
Checksum, SGB 3 1S73 0...1048575 0
Checksum, SGB 4 1S74 0...1048575 0
Checksum, SGB 5 1S75 0...1048575 0
Checksum, SGR 1 1S81 0...8388607 2108074
Checksum, SGR 2 1S82 0...8388607 2108074
Checksum, SGR 3 1S83 0...8388607 2108074
Checksum, SGR 4 1S84 0...8388607 5461
Checksum, SGR 5 1S85 0...8388607 5461
Checksum, SGR 6 1S86 0...8388607 0
Checksum, SGR 7 1S87 0...8388607 0
Checksum, SGR 8 1S88 0...8388607 0
Checksum, SGL 1 1S91 0...8388607 0
Checksum, SGL 2 1S92 0...8388607 0
Checksum, SGL 3 1S93 0...8388607 0
Checksum, SGL 4 1S94 0...8388607 0
Checksum, SGL 5 1S95 0...8388607 0
Checksum, SGL 6 1S96 0...8388607 0
Checksum, SGL 7 1S97 0...8388607 0
Checksum, SGL 8 1S98 0...8388607 0
Table 8.-2 Setting group 2
Variable Group/
Channel 2
(R, W, P)
Setting range Default
setting
Custo-
mer ’s
setting
Pickup value of element 51P 2S1 0.30...5.0 x I
n
(CT)
0.30 x I
n
(CT)
Operate time of element 51P (51P
TDLY)
2S2 0.05...300 s 0.05 s
Time/current characteristic for
element 51P
2S3 0...9 0
Time multiplier 51P TD IEC 2S4 0.05...1.00 0.05
Time multiplier 51P TD ANSI 2S5 1.0...15.0 1.0
Resetting time of element 51P
(51P RSET)
2S6 0.05...2.50 s 0.05 s
Pickup value of element 50P-1 2S7 0.50...35.0 x I
n
(CT)
0.50 x I
n
(CT)
Operate time of element 50P-1
(50P-1 TDLY)
2S8 0.04...300 s 0.04 s
168
REF610REF610
Feeder Protection Relay
Technical Reference Manual - ANSI Version
1MRS755535