ABB REF610 - Element ARC and L>; Relative Sensitivity of Lens Sensors

ABB REF610
176 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Feature Value
Operation accuracy
*
10...100% ±3% of the set pickup value and ±1 unit
Table 5.1.4.11.-5 Element ARC and L>
Feature Value
Element ARC
Set trip value ArcI> 0.5...35.0 x I
n
(CT)
Operate time < 15 ms
a)
ArcI
0
> 5.0...800% I
n
(CT)
Operate time < 17 ms
a)
Resetting time 30 ms
Operation accuracy ±7% of the set pickup value
L>
Activation time of L> < 15 ms
Resetting time 20 ms
a)
Applies only if a non-trip output contact (SO1...5) is used. If a trip output contact (PO1...3) is used, 2...3
ms will be added.
Fig. 5.1.4.11.-1 Relative sensitivity of lens sensors
72
REF610REF610
Feeder Protection Relay
Technical Reference Manual - ANSI Version
1MRS755535