Table 5.1.15.1.-9 Mapping of Modbus data: recorded data
Description HR/IR address
(.bit)
DI/Coil bit
address
Writeable Value range Comment
Fault record 601...628 See Structure 2
Event record 671...679 See Structure 3
Table 5.1.15.1.-10 Mapping of Modbus data: relay identification
Description HR/IR address
(.bit)
DI/Coil bit
address
Writeable Value range Comment
Type designation of the relay 701...708 ASCII chars, 2
chars/register
Table 5.1.15.1.-11 Mapping of Modbus data: real-time clock
Description HR/IR address
(.bit)
DI/Coil bit
address
Writeable Value range Comment
Time reading and setting 721...727 W See Structure 4
Table 5.1.15.1.-12 Mapping of Modbus data: additional analog data
Description HR/IR address
(.bit)
DI/Coil bit
address
Writeable Value range Comment
Thermal level 801 0...106 %
One-minute demand value 802 0...5000 0...50 x I
n
(CT)
Demand value during the specified
time range
803 0...5000 0...50 x I
n
(CT)
Maximum one-minute demand value
during the specified time range
804 0...5000 0...50 x I
n
(CT)
Element/phase which caused the trip 805 HI word 0...131071 See Table 5.1.17.-
3
806 LO word
Trip target code 807 0...21 See Table 5.1.17.-
3
Number of pickups of element 51P 808 0...999 Counter
Number of pickups of element 50P-1 809 0...999 Counter
Number of pickups of element 50P-2 810 0...999 Counter
Number of pickups of element 51N 811 0...999 Counter
Number of pickups of element 50N 812 0...999 Counter
Number of pickups of element 46 813 0...999 Counter
Number of trips of element 51P 814 0...65535 Counter
Number of trips of element 50P-1 815 0...65535 Counter
Number of trips of element 50P-2 816 0...65535 Counter
Number of trips of other elements 817 0...65535 Counter
Number of AR shots (shot 1) initiated
by the trip signal from element 50P-1
818 0...255 Counter
Number of AR shots (shot 1) initiated
by the digital input signal
819 0...255 Counter
Number of AR shots (shot 1) initiated
by the pickup or trip signal from
element 51P
820 0...255 Counter