Variable Actual settings
(R), channel 0
Group/Channel 1
(R, W, P)
Group/Channel 2
(R, W, P)
Setting range
Checksum, SGB 2 S72 1S72 2S72 0...1048575
Checksum, SGB 3 S73
c)
1S73 2S73 0...1048575
Checksum, SGB 4 S74
c)
1S74 2S74 0...1048575
Checksum, SGB 5 S75
c)
1S75 2S75 0...1048575
Checksum, SGR 1 S81 1S81 2S81 0...8388607
Checksum, SGR 2 S82 1S82 2S82 0...8388607
Checksum, SGR 3 S83 1S83 2S83 0...8388607
Checksum, SGR 4 S84 1S84 2S84 0...8388607
Checksum, SGR 5 S85 1S85 2S85 0...8388607
Checksum, SGR 6 S86
c)
1S86 2S86 0...8388607
Checksum, SGR 7 S87
c)
1S87 2S87 0...8388607
Checksum, SGR 8 S88
c)
1S88 2S88 0...8388607
Checksum, SGL 1 S91 1S91 2S91 0...8388607
Checksum, SGL 2 S92 1S92 2S92 0...8388607
Checksum, SGL 3 S93 1S93 2S93 0...8388607
Checksum, SGL 4 S94 1S94 2S94 0...8388607
Checksum, SGL 5 S95 1S95 2S95 0...8388607
Checksum, SGL 6 S96 1S96 2S96 0...8388607
Checksum, SGL 7 S97 1S97 2S97 0...8388607
Checksum, SGL 8 S98 1S98 2S98 0...8388607
a)
If the protection element is out of operation, the number indicating the currently used value will be displaced by “999” when the parameter is
read via the SPA bus and by dashes on the LCD.
b)
If the optional/O module has not been installed, a dash will be shown on the LCD and “999” when the parameter is read via the SPA bus.
c)
If the optional/O module has not been installed, a dash will be shown on the LCD and “9999999” when the parameter is read via the SPA bus.
Auto-reclose parameters
Table 5.1.17.-2 Auto-reclos e parameters
Description Parameter (R,
W, P), channel
0
Value
CB Closing time V121 0.1...10 s
Start delay of element 51P V122 0...300 s
Start delay of element 51N V123 0...300 s
Reclaim time V124 3...300 s
Cutout time V125 0.1...300 s
Dead time of shot 1 V126 0.1...300 s
Dead time of shot 2 V127 0.1...300 s
Dead time of shot 3 V128 0.1...300 s
SG1 V129 0...255
SG2 V130 0...1023
SG3 V131 0...31
The AR function can be activated either via the or with SPA parameter S25 by
setting the number of auto-reclose shots to 1, 2 or 3.
118
REF610REF610
Feeder Protection Relay
Technical Reference Manual - ANSI Version
1MRS755535