Table 5.1.4.10.-4 SGF3
Switch Function Default setting
SGF3/1 Disable of element 50P-1 0
SGF3/2 Disable of element 50P-2 0
SGF3/3 Disable of element 50N 0
SGF3/4 Disable of element 46 1
SGF3/5 Disable of element 49 1
SGF3/6 Disable of element ARC 1
*
When the switch is in position 1, the element is disabled.
SGF3/7 Disable of light signal output
*
When the switch is in position 1, the output is disabled.
1
ΣSGF3 120
Table 5.1.4.10.-5 SGF4
Switch Function Default setting
SGF4/1
Automatic doubling of the pickup value of element 50P-1
*
When the switch is in position 1, the set pickup value of the element is automatically doubled
at high inrush situations.
0
SGF4/2
Inverse-time operation of element 51P disabled by the pickup of element 50P-1
0
SGF4/3
Inverse-time operation of element 51P disabled by the pickup of element 50P-2
0
*
When the switch is in position 1, inverse-time operation is disabled.
SGF4/4 Automatic doubling of the pickup value of element 50N
*
When the switch is in position 1, the set pickup value of the element is automatically doubled
at high inrush situations.
Consider carefully when using this function!
0
SGF4/5
Inverse-time operation of element 51N disabled by the pickup of element 50N
*
When the switch is in position 1, inverse-time operation is disabled.
0
SGF4/6
Operation mode of light signal output
*
When the switch is in position 1, the light signal output is blocked by the trip signal from
element ARC.
0
ΣSGF4
0
Table 5.1.4.10.-6 SGF5
Switch Function Default setting
SGF5/1 Selection of the latching feature for programmable LED1 0
SGF5/2 Selection of the latching feature for programmable LED2 0
SGF5/3 Selection of the latching feature for programmable LED3 0
SGF5/4 Selection of the latching feature for programmable LED4
0
SGF5/5 Selection of the latching feature for programmable LED5 0
SGF5/6 Selection of the latching feature for programmable LED6 0
62
REF610REF610
Feeder Protection Relay
Technical Reference Manual - ANSI Version
1MRS755535