Switching between setting groups via a digital input has a higher
priority than via the HMI or with the parameter V150.
The setting values can be altered via the HMI or with a PC provided with Relay
Setting Tool.
Before the relay is connected to a system it must be assured that the relay has been
given the correct settings. If there is any doubt, the setting values should be read
with the relay trip circuits disconnected or tested with current injection; refer to
Section 8. Check lists for additional information.
Table 5.1.4.10.-1 Setting values
Setting Description Setting range Default setting
51P/I
n
(CT) Pickup value of element 51P 0.30...5.00 x I
n
(CT) 0.30 x I
n
(CT)
51P TDLY Operate time of element 51P 0.05...300 s 0.05 s
51P MODE Time/current characteristic for
element 51P
0...9 0
51P TD IEC Time multiplier 51P TD IEC 0.05...1.00 0.05
51P TD ANSI Time multiplier 51P TD ANSI 1.0...15.0 1.0
51P RSET Resetting time of element 51P 0.05...2.50 s 0.05 s
50P-1/I
n
(CT) Pickup value of element 50P-1 0.50...35.0 x I
n
(CT) 0.50 x I
n
(CT)
50P-1 TDLY Operate time of element 50P-1 0.04...300 s 0.04 s
50P-2/I
n
(CT) Pickup value of element 50P-2 0.50...35.0 x I
n
(CT) 0.50 x I
n
(CT)
50P-2 TDLY Operate time of element 50P-2 0.04...30.0 s 0.04 s
51N/I
n
(CT) Pickup value of element 51N 1.0...100% I
n
(CT) 1.0% I
n
(CT)
51N TDLY Operate time of element 51N 0.05...300 s 0.05 s
51N MODE Time/current characteristic for
element 51N
0...9 0
51N TD IEC Time multiplier 51N TD IEC 0.05...1.00 0.05
51N TD ANSI Time multiplier 51N TD ANSI 1.015.0 1.0
51N RSET Resetting time of element 51N 0.05...2.50 s 0.05 s
50N/I
n
(CT) Pickup value of element 50N 5.0...800% I
n
(CT) 5.0% I
n
(CT)
50N TDLY Operate time of element 50N 0.05...300 s 0.05 s
46 PICKUP Pickup value of element 46 Pickup 10...100% 100 %
46 TDLY Operate time of element 46 Pickup 1...300 s 60 s
FLA Full load current 0.30...1.50 x I
n
(CT) 0.30 x I
n
(CT)
τ Time constant of element 49 1...200 min 1 min
49 Alarm Alarm level of element 49 50...100% 49 trip 95% 49 trip
CBFAIL Operate time of CBFAIL 0.10...60.0 s 0.10 s
79 Number of AR shots 0 = AR is not in use
1 = shot 1
2 = shot 1 and 2
3 = shot 1, 2 and 3
0
Arc50P Current limit Arc51P of element ARC 0.50...35.0 x I
n
(CT) 2.50 x I
n
(CT)
ARC50N Current limit Arc51N of element ARC 5.0...800% I
n
(CT) 20.0% I
n
(CT)