Table 5.1.4.10.-12 SG3
Switch Function Default setting
SG3/1 Disable of the AR function by the trip signal from element 50P-2 1
SG3/2 Dsable of the AR function by the trip signal from element 50N 1
SG3/3 Disable of the AR function by the alarm signal from element 49 1
SG3/4 Disable of the AR function by the trip signal from element 46 1
*
When the switch is in position 1, the AR function is disabled.
SG3/5 Resetting targets at CB reclosing 0
*
When the switch is in position 1, targets are reset when the AR function
issues a reclosing command to the circuit breaker.
ΣSG3 15
New trip target timer
The new trip target timer can be configured to allow a second trip target on the
LCD. When several protection elements trip, the first trip target is displayed until
the time, as specified by the NEW TRIP IND. setting value, has expired. After this,
a new trip target can displace the old one. The basic protection functions are not
affected by the NEW TRIP IND. setting.
Table 5.1.4.10.-13 New trip target timer
Setting Description Setting range Default setting
New trip target New trip target timer in minutes 0...998 60
No new trip target allowed until the
previous one has been manually
cleared.
999 -
Non-volatile memory settings
Non-volatile memory is backed up by a battery; the battery must be
inserted and charged.
The table below presents data which can be configured to be stored in the non-
volatile memory. All of the functions mentioned below can be selected separately
with switches 1...5 either via the HMI or the SPA bus.
Table 5.1.4.10.-14 Memory settings
Setting Switch Function Default setting
Non-volatile
memory settings
1
*
0 = operation target messages and LEDs
are cleared
*
1 = operation target messages and LEDs
are retained
1
2
*
1 = disturbance recorder data is retained
a)
1
3
*
1 = event codes are retained
a)
1
68