Defining deadbands for event reporting
*
Defining scaling factors for analog values
Table 5.1.16.2.-1 Binary data
Description DNP point
address
Event class UR enable Value range Comment
Pickup signal from element 51P 0 1 1 0/1 1 = activated
Trip signal from element 51P 1 1 1 0/1 1 = activated
Pickup signal from element 50P-1 2 1 1 0/1 1 = activated
Trip signal from element 50P-1 3 1 1 0/1 1 = activated
Pickup signal from 50P-2 4 1 1 0/1 1 = activated
Trip signal from element 50P-2 5 1 1 0/1 1 = activated
Pickup signal from element 51N 6 1 1 0/1 1 = activated
Trip signal from element 51N 7 1 1 0/1 1 = activated
Pickup signal from element 50P-1 8 1 1 0/1 1 = activated
Trip signal from element 50P-1 9 1 1 0/1 1 = activated
Pickup signal from element 46 10 1 1 0/1 1 = activated
Trip signal from element 46 11 1 1 0/1 1 = activated
Pickup signal from element 49 12 1 1 0/1 1 = activated
Alarm signal from element 49 13 1 1 0/1 1 = activated
Trip signal from element 49 14 1 1 0/1 1 = activated
Trip signal from element ARC (light and
current)
15 1 1 0/1 1 = activated
Trip signal from element ARC (DI and
current)
16 1 1 0/1 1 = activated
Light signal output 17 1 1 0/1 1 = detected
Trip lockout signal 18 1 1 0/1 1 = activated
External trip signal 19 1 1 0/1 1 = activated
CBFAIL 20 1 1 0/1 1 = failure
Shot 1 21 1 1 0/1 1 = initiated
Shot 2 22 1 1 0/1 1 = initiated
Shot 3 23 1 1 0/1 1 = initiated
CB position 24 1 1 0/1 1 = closed
Definite trip alarm signal 25 1 1 0/1 1 = activated
AR lockout signal 26 1 1 0/1 1 = activated
Open CB command 27 1 1 0/1 1 = activated
Close CB command 28 1 1 0/1 1 = activated
CB reclosing failed signal 29 1 1 0/1 1 = activated
CB reclosing disabled 30 1 1 0/1 1 = activated
AR cancelled 31 1 1 0/1 1 = activated
PO1 32 1 1 0/1 1 = activated
PO2 33 1 1 0/1 1 = activated
PO3 34 1 1 0/1 1 = activated
SO1 35 1 1 0/1 1 = activated
SO2 36 1 1 0/1 1 = activated
SO3 37 1 1 0/1 1 = activated
104
REF610REF610
Feeder Protection Relay
Technical Reference Manual - ANSI Version
1MRS755535