105
Description DNP point
address
Event class UR enable Value range Comment
SO4 38 1 1 0/1 1 = activated
SO5 39 1 1 0/1 1 = activated
DI1 40 1 1 0/1 1 = activated
DI2 41 1 1 0/1 1 = activated
DI3 42 1 1 0/1 1 = activated
DI4 43 1 1 0/1 1 = activated
DI5 44 1 1 0/1 1 = activated
Disturbance recorder 45 1 1 0/1 1 = triggered
0 = cleared
HMI Setting password 46 1 1 0/1 1 = opened
0 = closed
IRF 47 1 1 0/1 1 = activated
Warning 48 1 1 0/1 1 = activated
SPA event overflow 49 1 1 0/1 1 = activated
HMI Communication password 50 1 1 0/1 1 = opened
0 = closed
Table 5.1.16.2.-2 Analog data
Description DNP point
address
Event class UR enable Deadband Value range Internal
scaling
factor (ix = 0)
Phase current I
a
xI
n
(CT) 02110...5000 100
Phase current I
b
xI
n
(CT) 12110...5000 100
Phase current I
c
xI
n
(CT) 22110...5000 100
Ground-fault current x I
n
(CT) 32110...20000 10
Phase unbalance 42110...100 100
Thermal level 52110...106 100
One-minute demand value 62110...5000 100
Demand value during the specified
time range
72110...5000 100
Maximum one-minute demand
value during the specified time
range
82110...5000 100
Table 5.1.16.2.-3 Counters
Description DNP point
address
Event class UR enable Deadband Value range
Number of pickups of element 51P 0 3 1 1 0...999
Number of pickups of element 50P-1 1 3 1 1 0...999
Number of pickups of element 50P-2 2 3 1 1 0...999
Number of pickups of element 51N 3 3 1 1 0...999
Number of pickups of element 50N 4 3 1 1 0...999
Number of pickups of element 46 5 3 1 1 0...999
Number of trips of element 51P 6 3 1 1 0...65535
Number of trips of element 50P-1 7 3 1 1 0...65535
Number of trips of element 50P-2 8 3 1 1 0...65535
Feeder Protection Relay
Technical Reference Manual - ANSI Version
REF610REF610
1MRS755535