Table 5.1.17.1.-7 Event codes E25...E42
Channel Event Description Weighting
factor
Default
value
1 E25 Pickup signal from element 49 activated 1 0
1 E26 Pickup signal from element 49 reset 2 0
1 E27 Alarm signal from element 49 activated 4 1
1 E28 Alarm signal from element 49 reset 8 0
1 E29 Trip signal from element 49 activated 16 1
1 E30 Trip signal from element 49 reset 32 0
1 E31 Trip signal from element ARC (light and
current) activated
64 1
1 E32 Trip signal from element ARC (light and
current) reset
128 0
1 E33 Trip signal from element ARC (DI and
current) activated
256 0
1 E34 Trip signal from element ARC (DI and
current) reset
512 0
1 E35 Light signal output activated 1024 0
1 E36 Light signal output reset 2048 0
1 E37 Trip lockout signal activated 4096 1
1 E38 Trip lockout signal reset 8192 0
1 E39 External trip signal activated 16384 0
1 E40 External trip signal reset 32768 0
1 E41 CBFAIL activated 65536 0
1 E42 CBFAIL reset 131072 0
Default value of event mask 1V157 4180
Channel 2
Table 5.1.17.1.-8 Event codes E1...E16
Channel Event Description Weighting
factor
Default
value
2 E1 PO1 activated 1 1
2 E2 PO1 reset 2 1
2 E3 PO2 activated 4 0
2 E4 PO2 reset 8 0
2 E5 PO3 activated 16 0
2 E6 PO3 reset 32 0
2 E7 SO1 activated 64 0
2 E8 SO1 reset 128 0
2 E9 SO2 activated 256 0
2 E10 SO2 reset 512 0
2 E11 SO3 activated 1024 0
2 E12 SO3 reset 2048 0
2 E13 SO4 activated 4096 0
2 E14 SO4 reset 8192 0
134
REF610REF610
Feeder Protection Relay
Technical Reference Manual - ANSI Version
1MRS755535