137
Table 5.1.18.-1 IRF codes
Fault code Type of fault
4 Error in output relay PO1
5 Error in output relay PO2
6 Error in output relay PO3
7 Error in output relay SO1
8 Error in output relay SO2
9 Error in the enable signal for output relay PO1, PO2, SO1 or SO2
10, 11, 12 Error in the feedback, enable signal or output relay PO1, PO2, SO1
or SO2
13 Error in optional output relay SO3
14 Error in optional output relay SO4
15 Error in optional output relay SO5
16 Error in the enable signal for optional output relay SO3, SO4 or SO5
17, 18, 19 Error in the feedback, enable signal or optional output relay SO3,
SO4 or SO5
20, 21 Auxiliary voltage dip
30 Faulty program memory
50, 59 Faulty work memory
51, 52, 53
a)
, 54, 56 Faulty parameter memory
b)
55 Faulty parameter memory, calibration parameters
80 Optional I/O module missing
81 Optional I/O module unknown
82 Optional I/O module configuration error
85 Power supply module faulty
86 Power supply module unknown
90 Hardware configuration error
95 Communication module unknown
104 Faulty configuration set (for IEC 60870-5-103)
131, 139, 195, 203,
222, 223
Internal reference voltage error
240 Faulty input, Light sensor 2
241 Faulty input, Light sensor 1
253 Error in the measuring unit
a)
Can be corrected by restoring factory settings for CPU.
b)
All settings will be zero during the fault.
For further information on internal relay faults, refer to the Operator’s Manual.
Warnings
In case of a warning, the relay continues to operate except for those protection
functions possibly affected by the fault, and the green target LED (ready) remains lit
as during normal operation. Further, a fault target message, which depending on the
type of fault includes a fault code, appears on the LCD. If more than one type of
Feeder Protection Relay
Technical Reference Manual - ANSI Version
REF610REF610
1MRS755535