97
Description HR/IR address (.bit) DI/Coil bit
address
Writeable Value
range
Comment
Trip signal from element ARC (light and
current) CD
410.15 32
Trip signal from element ARC (light and
DI)
411.00 33 0/1 1 = activated
Trip signal from element ARC (light and
DI) CD
411.01 34
Light signal output 411.02 35 0/1 1 = activated
Light signal output CD 411.03 36
Trip lockout signal 411.04 37 0/1 1 = activated
Trip lockout signal CD 411.05 38
External trip signal 411.06 39 0/1 1 = activated
External trip signal CD 411.07 40
CBFAIL 411.08 41 0/1 1 = failure
CBFAIL CD 411.09 42
Shot 1 411.10 43 0/1 1 = initiated
Shot 1 CD 411.11 44
Shot 2 411.12 45 0/1 1 = initiated
Shot 2 CD 411.13 46
Shot 3 411.14 47 0/1 1 = initiated
Shot 3 CD 411.15 48
CB position 412.00 49 0/1 1 =closed
0 = open
CB position CD 412.01 50
Definite trip alarm signal 412.02 51 0/1 1 = activated
Definite trip alarm signal CD 412.03 52
AR lockout signal 412.04 53 0/1 1 = activated
AR lockout signal CD 412.05 54
Open CB command 412.06 55 0/1 1 = activated
Open CB command CD 412.07 56
Close CB command 412.08 57 0/1 1 = activated
Close CB command CD 412.09 58
CB reclosing failed signal 412.10 59 0/1 1 = activated
CB reclosing failed signal CD 412.11 60
CB reclosing disabled 412.12 61 0/1 1 = activated
CB reclosing disabled CD 412.13 62
AR cancelled 412.14 63 0/1 1 = activated
AR cancelled CD 412.15 64
PO1 413.00 65 0/1 1 = activated
PO1 CD 413.01 66
PO2 413.02 67 0/1 1 = activated
PO2 CD 413.03 68
PO3 413.04 69 0/1 1 = activated
PO3 CD 413.05 70
SO1 413.06 71 0/1 1 = activated
Feeder Protection Relay
Technical Reference Manual - ANSI Version