125
Description Parameter R, W, P Value
Resetting of relay state data C W 0 = Reset E50 and E51
1 = Reset only E50
2 = Reset only E51
4 = Reset all events including E51 except for
E50
Time reading and setting T R, W SS.sss
Date and time reading and setting D R, W YY-MM-DD HH.MM;SS.sss
Type designation of the relay F R REF610
Unlatching output contacts V101 W 1 = Unlatch
Clearing targets and memorized values and
unlatching contacts (master reset)
V102 W 1 = Clear and unlatch
Resetting of trip lockout V103 W 1 = Reset
Rated frequency V104 R, W (P) 50 or 60 Hz
Time setting range for demand values in
minutes
V105 R, W 0...999 min
Non-volatile memory settings V106 R, W 0...31
Time setting for disabling new trip targets on the
LCD
V108 R, W (P) 0...999 min
Testing the self-supervision V109 W (P) 1 = Self-supervision output contact is
activated and the READY target LED starts
to flash
0 = Normal operation
LED test for pickup and trip targets V110 W (P) 0 = Pickup and trip LEDs off
1 = Trip LED on, pickup LED off
2 = Pickup LED on, trip LED off
3 = and trip LEDs on
LED test for programmable LEDs V111 W (P) 0...255
Trip-circuit supervision V113 R, W 0 = Not in use
1 = In use
Store counter
a)
V114 R 0...65535
Remote control of setting group V150 R, W 0 = Setting group 1
1 = Setting group 2
Entering the SPA password for settings V160 W 1...999
Changing the SPA password or taking the
password protection into use
V161 W (P) 1...999
Changing the HMI Setting password V162 W 1...999
Changing the HMI Communication password V163 W 1...999
Clearing trip counters or AR counter V166 W (P) 1 = Clear trip counters
2 = Clear AR counters
Restoring factory settings V167 W (P) 2 = Restore factory settings for CPU
3 = Restore factory settings for DNP
Warning code V168 R 0...63
b)
IRF code V169 R 0...255
b)
Unit address of the relay V200 R, W 1...254
Data transfer rate (SPA), kbps V201 R, W 9.6/4.8
Rear communication V202 W 1 = Rear connector activated