Recorded data Event (R) Value
n Channel 1 n-1 Channel 2 n-2 Channel 3 n-3 Channel 4 n-4 Channel 5
Maximum pickup
phase current I
a
1V8 2V8 3V8 4V8 5V8 0...50 x I
n
(CT)
Maximum pickup
phase current I
b
1V9 2V9 3V9 4V9 5V9 0...50 x I
n
(CT)
Maximum pickup
phase current I
c
1V10 2V10 3V10 4V10 5V10 0...50 x I
n
(CT)
Maximum pickup
ground-fault current
1V11 2V11 3V11 4V11 5V11 0...2000%
Pickup duration of
element 51P
1V12 2V12 3V12 4V12 5V12 0...100%
Pickup duration of
element 50P-1
1V13 2V13 3V13 4V13 5V13 0...100%
Pickup duration of
element 50P-2
1V14 2V14 3V14 4V14 5V14 0...100%
Pickup duration of
element 51N
1V15 2V15 3V15 4V15 5V15 0...100%
Pickup duration of
element 50N
1V16 2V16 3V16 4V16 5V16 0...100%
Pickup duration of
element 46
1V17 2V17 3V17 4V17 5V17 0...100%
Pickup duration of
external trip
1V18 2V18 3V18 4V18 5V18 0/100%
Trip number of AR
sequence
1V19 2V19 3V19 4V19 5V19 0...255
Pickup duration of
element ARC (local)
1V20 2V20 3V20 4V20 5V20 0/100%
Pickup duration of
element ARC (remote)
1V21 2V21 3V21 4V21 5V21 0/100%
Time stamp of the
recorded data, date
1V22 2V22 3V22 4V22 5V22 YY-MM-DD
Time stamp of the
recorded data, time
1V23 2V23 3V23 4V23 5V23 HH.MM;
SS.sss
a)
If the thermal protection has been set out of operation (SGF3/5), dashes will be shown on the LCD and “999” when the parameter is read via
the SPA bus.
122
REF610REF610
Feeder Protection Relay
Technical Reference Manual - ANSI Version
1MRS755535