EasyManua.ls Logo

ABB REG650 - Page 295

ABB REG650
728 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Note that angle between U
3N
and U
3T
is typically close to 180°.
en06000448.vsd
U
3N
U
3T
- DU
3
+
- U
3
+
- U
3N
+
+
U
3T,L1
-
+
U
3T,L2
-
+
U
3T,L3
-
IEC06000448 V2 EN
Figure 144:
Generator 3
rd
harmonic voltage characteristic at normal operation
The generator is modeled as parts of a winding where a 3
rd
harmonic voltage is
induced along the winding, represented by the end voltages U
3N
(voltage drop across
resistor) and U
3T
in the figure. Via the winding capacitances to earth and the neutral
point resistor there will be a small 3
rd
harmonic current, giving the voltages U
3N
and
U
3T
. The 3
rd
harmonic voltage in the generator neutral point (U
3N
) will be close to zero
in case of a stator earth-fault close to the neutral. This fact alone can be used as an
indication of stator earth-fault. To enable better sensitivity and stability also
measurement of the generator's 3
rd
harmonic voltage U
3T
is also used. In addition to
the decrease of U
3N
the generator voltage U
3T
will increase under the stator earth-fault
close to the generator neutral point. Therefore the 3
rd
harmonic voltage U
3T
, (which
is a zero sequence voltage) is used by the protection. In the 3
rd
harmonic voltage
differential protection algorithm equation
94 is used:
1MRK 502 048-UEN A Section 9
Voltage protection
289
Technical manual

Table of Contents

Other manuals for ABB REG650

Related product manuals