EasyManua.ls Logo

ABB REG650 - Technical Data

ABB REG650
728 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10.3.7 Technical data
Table 197: SAPFRC technical data
Function
Range or value Accuracy
Operate value, start function (-10.00-10.00) Hz/s ± 10.0 mHz/s
Operate value, restore
enable frequency
(45.00 - 65.00) Hz ± 2.0 mHz
Timers (0.000 - 60.000) s <130 ms
Operate time, start function At 50 Hz: 100 ms typically
At 60 Hz: 80 ms typically
-
Section 10 1MRK 502 048-UEN A