Name Type Default Description
QC3_CL BOOLEAN 0 QC3 is in closed position
QC9_OP BOOLEAN 0 QC9 is in open position
QC9_CL BOOLEAN 0 QC9 is in closed position
VOLT_OFF BOOLEAN 0 There is no voltage on the line and not VT (fuse)
failure
VOLT_ON BOOLEAN 0 There is voltage on the line or there is a VT (fuse)
failure
QB9_EX1 BOOLEAN 0 External condition for apparatus QB9
QB9_EX2 BOOLEAN 0 External condition for apparatus QB9
QB9_EX3 BOOLEAN 0 External condition for apparatus QB9
QB9_EX4 BOOLEAN 0 External condition for apparatus QB9
QB9_EX5 BOOLEAN 0 External condition for apparatus QB9
Table 254: DB_BUS_A Output signals
Name Type Description
QA1CLREL BOOLEAN Closing of QA1 is allowed
QA1CLITL BOOLEAN Closing of QA1 is forbidden
QB61REL BOOLEAN Switching of QB61 is allowed
QB61ITL BOOLEAN Switching of QB61 is forbidden
QB1REL BOOLEAN Switching of QB1 is allowed
QB1ITL BOOLEAN Switching of QB1 is forbidden
QC1REL BOOLEAN Switching of QC1 is allowed
QC1ITL BOOLEAN Switching of QC1 is forbidden
QC2REL BOOLEAN Switching of QC2 is allowed
QC2ITL BOOLEAN Switching of QC2 is forbidden
QB1OPTR BOOLEAN QB1 is in open position
QB1CLTR BOOLEAN QB1 is in closed position
VPQB1TR BOOLEAN Switch status of QB1 is valid (open or closed)
Table 255: DB_BUS_B Output signals
Name
Type Description
QA2CLREL BOOLEAN Closing of QA2 is allowed
QA2CLITL BOOLEAN Closing of QA2 is forbidden
QB62REL BOOLEAN Switching of QB62 is allowed
QB62ITL BOOLEAN Switching of QB62 is forbidden
QB2REL BOOLEAN Switching of QB2 is allowed
QB2ITL BOOLEAN Switching of QB2 is forbidden
QC4REL BOOLEAN Switching of QC4 is allowed
QC4ITL BOOLEAN Switching of QC4 is forbidden
Table continues on next page
1MRK 502 048-UEN A Section 12
Control
393
Technical manual