Name Values (Range) Unit Step Default Description
CTprim4 1 - 99999 A 1 1000 Rated CT primary current
CTStarPoint5 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec5 0.1 - 10.0 A 0.1 1.0 Rated CT secondary current
CTprim5 1 - 99999 A 1 1000 Rated CT primary current
VTsec6 0.001 - 999.999 V 0.001 110 Rated VT secondary voltage
VTprim6 0.001 - 9999.999 kV 0.001 132 Rated VT primary voltage
VTsec7 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim7 0.001 - 9999.999 kV 0.001 132.000 Rated VT primary voltage
VTsec8 0.001 - 999.999 V 0.001 110 Rated VT secondary voltage
VTprim8 0.001 - 9999.999 kV 0.001 132 Rated VT primary voltage
VTsec9 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim9 0.001 - 9999.999 kV 0.001 132.000 Rated VT primary voltage
VTsec10 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim10 0.001 - 9999.999 kV 0.001 132.000 Rated VT primary voltage
Section 3 1MRK 502 048-UEN A
Analog inputs
52
Technical manual

Table of Contents

Other manuals for ABB REG650