CharPPZx
CharPGZx
where x=1- 5
Mho characteristic
CharPPZx
CharPGZx
where x=1- 5
Quadrilateral characteristic
CharPPZx
CharPGZx
where x=1- 5
Mho and Quadrilateral characteristic
R
X
Z1
Z2
Z3
Z4
Z5
R
X
Z1
Z2
Z3
Z4
Z5
ANSI11000265_1_en.vsd
R
X
Z3
Z2
Z1
Z4
Z5
ANSI11000265 V1 EN
Figure 64: Impedance characteristic
Complex characteristic can be formed with the ZQMPDIS ( 21) function. Figure 65 shows
for example, when zone 1 is set to combined quadrilateral and mho characteristic, zone 2
is set to forward mho characteristic, zone 3 is set to reverse mho characteristic and, zone
4 and 5 are set to quadrilateral characteristic.
1MRK 506 334-UUS A Section 6
Impedance protection
131
Application manual