tINNonDir is the definite time delay for the non directional ground-fault current
protection, given in s.
OpVN is set Enabled to activate the trip function of the residual voltage protection.
tVN is the definite time delay for the trip function of the residual voltage protection, given
in s.
7.8 Time delayed 2-step undercurrent protection
UC2PTUC (37)
7.8.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Time delayed 2-step undercurrent
protection
UC2PTUC
3I<
2
IEC09000131 V2 EN
37
7.8.2 Application
Time delayed 2-step undercurrent protection (UC2PTUC ,37) can be used wherever a
“low current” signal is needed. The main application is as a local criterion to increase
security when transfer trip schemes are used. Two different application examples for the
undercurrent protection function are given below. The examples are a power transformer
directly connected to the feeding line and a line connected shunt reactor operating on a
Section 7 1MRK 506 334-UUS A
Current protection
224
Application manual