6.1.3.4 Mho characteristics
Load impedance limitation, with load encroachment function activated
The parameters for load encroachment shaping of the characteristic are found in the
description of Faulty phase identification with load encroachment for mho (FMPSPDIS).
Load impedance limitation, without load encroachment function
The following instruction is valid when the load encroachment function or blinder
function is not activated (BlinderMode=Disabled). If the load encroachment or blinder
function is to be used for all or some of the measuring zones, the load limitation for those
zones according to this chapter can be omitted. Check the maximum permissible resistive
reach for any zone to ensure that there is a sufficient setting margin between the relay
boundary and the minimum load impedance. The minimum load impedance (Ω/phase) is
calculated as:
2
min
V
Zload
S
=
EQUATION1753-ANSI V1 EN (Equation 57)
Where:
V is the minimum phase-to-phase voltage in kV
S is the maximum apparent power in MVA.
The load impedance [Ω/phase] is a function of the minimum operation voltage and the
maximum load current:
min
max
3 I
V
Zload =
×
EQUATION1754-ANSI V1 EN (Equation 58)
Minimum voltage V
min
and maximum current I
max
are related to the same operating
conditions. Minimum load impedance occurs normally under emergency conditions.
To avoid load encroachment for the phase-to-ground measuring elements, the set
impedance reach of any distance protection zone must be less than 80% of the minimum
load impedance.
Section 6 1MRK 506 334-UUS A
Impedance protection
138
Application manual