EasyManua.ls Logo

ABB REL650 - IEC61850-8-1 Communication Protocol

ABB REL650
516 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Section 16 Station communication
16.1 IEC61850-8-1 communication protocol
16.1.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
IEC 61850-8-1 communication protocol IEC 61850-8-1 - -
16.1.2 Application
IEC 61850-8-1 communication protocol allows vertical communication to HSI clients
and allows horizontal communication between two or more intelligent electronic devices
(IEDs) from one or several vendors to exchange information and to use it in the
performance of their functions and for correct co-operation.
GOOSE (Generic Object Oriented Substation Event), which is a part of IEC 61850–8–1
standard, allows the IEDs to communicate state and control information amongst
themselves, using a publish-subscribe mechanism. That is, upon detecting an event, the
IED(s) use a multi-cast transmission to notify those devices that have registered to receive
the data. An IED can, by publishing a GOOSE message, report its status. It can also
request a control action to be directed at any device in the network.
Figure 215 shows the topology of an IEC 61850–8–1 configuration. IEC 61850–8–1
specifies only the interface to the substation LAN. The LAN itself is left to the system
integrator.
1MRK 506 334-UUS A Section 16
Station communication
459
Application manual

Table of Contents

Other manuals for ABB REL650

Related product manuals