11.1.3.3 Single circuit breaker with double busbar, internal voltage selection
Bus 1
Bus 2
Line
Fuse
VT
Fuse
VT
ANSI10000196-2-en.vsd
SMAI
GRP_OFF
SMAI
SMAI
VBus1
VBus2
VLine
Fuse
VT
SESRSYN (25)
V3PB1*
V3PB2*
V3PL1*
V3PL2*
BLOCK
BLKSYNCH
BLKSC
BLKENERG
BUS1_OP
BUS1_CL
BUS2_OP
BUS2_CL
LINE1_OP
LINE1_CL
LINE2_OP
LINE2_CL
VB1OK
VB1FF
VB2OK
VB2FF
VL1OK
VL1FF
VL2OK
VL2FF
STARTSYN
TSTSYNCH
TSTSC
TSTENERG
AENMODE
MENMODE
SYNOK
AUTOSYOK
AUTOENOK
MANSYOK
MANENOK
TSTSYNOK
TSTAUTSY
TSTMANSY
TSTENOK
VSELFAIL
B1SEL
B2SEL
L1SEL
L2SEL
SYNPROGR
SYNFAIL
FRDIFSYN
FRDERIVA
VOKSC
VDIFFSC
FRDIFFA
PHDIFFA
FRDIFFM
PHDIFFM
INADVCLS
VDIFFME
FRDIFFME
PHDIFFME
Vbus
VLine
MODEAEN
MODEMEN
189
289
BKR1
52
ANSI10000196 V2 EN
Figure 134: Connection of the SESRSYN (25) function block in a single breaker,
double busbar arrangement with internal voltage selection.
When internal voltage selection is needed, the voltage transformer circuit connections are
made according to figure
134. The voltage from busbar1 VT is connected to V3PB1 and
the voltage from busbar2 VT is connected to V3PB2. The voltage from the line VT is
connected to V3PL1. The positions of the disconnectors and VT fuses shall be connected
as shown in figure 134. The voltage selection parameter CBConfig is set to Double bus.
Section 11 1MRK 506 334-UUS A
Control
296
Application manual