Lock-out
RXMD1
11
12
21
MAIN ZAK CLOSE
CLOSE COMMAND
OR
SMBRREC (79)
OR
CCRBRF (50BF)
BJ-TRIP
ZCVPSOF-TRIP
INHIBIT
UNSUCCL
TRBU
ANSI11000168_2_en.vsd
ANSI11000168 V1 EN
Figure 137: Lock-out arranged with an external Lock-out relay
CLOSE COMMAND
OR
SMBRREC (79)
OR
CCRBRF (50BF)
BU-TRIP
ZCVPSOF-TRIP
INHIBIT
UNSUCCL
TRBU
SMPPTRC (94)
AND
RESET LOCK-OUT
OR
OR
SESRSYN (25)
SOFTWARE
OR IO RESET
AUTOSTOP
MANENOK
MAN CLOSE
SMBRREC (79) CLOSE
CLLKOUT
RSTLKOUT
SETLKOUT
ANSI11000167_1_en.vsd
ANSI11000167 V1 EN
Figure 138: Lock-out arranged with internal logic with manual closing going through
in IED
11.2.2.13 Automatic continuation of the reclosing sequence
SMBRREC (79) function can be programmed to proceed to the following reclosing shots
(if multiple shots are selected) even if start signals are not received from the protection
functions, but the breaker is still not closed. This is done by setting parameter AutoCont =
Enabled and tAutoContWait to the required delay for the function to proceed without a
new start.
Section 11 1MRK 506 334-UUS A
Control
310
Application manual