Set
tSendMin
= 0 s
Set
Unblock
=
Disabled
(Set to
NoRestart
if Unblocking scheme with no alarm for loss of guard is to be
used.
Set to
Restart
if Unblocking scheme with alarm for loss of guard is to be used)
Set
tSecurity
= 0.035 s
12.1.3.2 Delta blocking scheme
Set
Operation
=
Enabled
Set
SchemeType
=
DeltaBlocking
Set
tCoord
= 0 s
Set
tSendMin
= 0 s
Set
Unblock
=
Disabled
(Set to
NoRestart
if Unblocking scheme with no alarm for loss of guard is to be
used.
Set to
Restart
if Unblocking scheme with alarm for loss of guard is to be used)
Set
tSecurity
= 0.035 s
Set
DeltaI
= 10 %IB
Set
DeltaV
= 5 %VB
Set
Delta3I0
= 10 %IB
Set
Delta3V0
= 5 %VB
12.1.3.3 Permissive underreaching scheme
Set
Operation
=
Enabled
Set
SchemeType
=
Permissive UR
Set
tCoord
= 0 ms
Set
tSendMin
= 0.1 s
Set
Unblock
=
Disabled
Set
tSecurity
= 0.035 s
12.1.3.4 Permissive overreaching scheme
Set
Operation
=
Enabled
Set
Scheme type
=
Permissive OR
Set
tCoord
= 0 ms
Set
tSendMin
= 0.1 s (0 s in parallel line applications)
Set
Unblock
=
Disabled
Set
tSecurity
= 0.035 s
Section 12 1MRK 506 334-UUS A
Scheme communication
398
Application manual