EasyManua.ls Logo

ABB REL650 - Breaker Failure Protection

ABB REL650
516 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
where:
I
kmax
Maximum primary fundamental frequency current for close-in forward and reverse
faults (A)
I
kzone1
Maximum primary fundamental frequency current for faults at the end of zone 1
reach (A)
I
pn
The rated primary CT current (A)
I
sn
The rated secondary CT current (A)
I
n
The nominal current of the protection IED (A)
R
CT
The secondary resistance of the CT (W)
R
L
The resistance of the secondary wire and additional load (W). In solidly grounded
systems the loop resistance containing the phase and neutral wires should be used
for phase-to-ground faults and the resistance of the phase wire should be used for
three-phase faults.
In isolated or high impedance grounded systems the resistance of the single
secondary wire always can be used.
S
R
The burden of an IED current input channel (VA). S
R
=0.010 VA/channel for I
r
=1 A
and S
r
=0.250 VA/channel for I
r
=5 A
a This factor is a function of the primary time constant for the dc component in the
fault current.
a= 2 for the primary time constant T
p
£ 50 ms
a = 3 for the primary time constant T
p
> 50 ms
k
A factor of the primary time constant for the dc component in the fault current for a
three-phase fault at the set reach of zone 1.
k = 4 for the primary time constant T
p
£ 30 ms
k = 6 for the primary time constant T
p
> 30 ms
18.1.6.2 Breaker failure protection
The CTs must have a rated equivalent secondary e.m.f. E
al
that is larger than or equal to
the required secondary e.m.f. E
alreq
below:
1MRK 506 334-UUS A Section 18
Requirements
493
Application manual

Table of Contents

Other manuals for ABB REL650

Related product manuals