GlobalBaseSel: Selects the global base value group used by the function to define (IBase),
(VBase) and (SBase).
99001019_ansi.vsd
~~
E
A
d
A
= const
d
B
= f(t)
E
B
A B
Z
SA
Z
SB
Z
L
R
ANSI99001019 V1 EN
Figure 76: Protected power line as part of a two-machine system
Reduce the power system with protected power line into equivalent two-machine system
with positive sequence source impedances Z
SA
behind the IED and Z
SB
behind the remote
end bus B. Observe a fact that these impedances can not be directly calculated from the
maximum three-phase short circuit currents for faults on the corresponding busbar. It is
necessary to consider separate contributions of different connected circuits.
The required data is as follows:
EQUATION1728 V1 EN
Rated system voltage
EQUATION1729 V1 EN
Minimum expected system voltage under critical system
conditions
EQUATION1730 V1 EN
Rated system frequency
EQUATION1731 V1 EN
Rated primary voltage of voltage protection transformers used
EQUATION1732 V1 EN
Rated secondary voltage of voltage instrument transformers used
EQUATION1326 V1 EN
Rated primary current of current protection transformers used
Table continues on next page
1MRK 506 334-UUS A Section 6
Impedance protection
159
Application manual