EasyManua.ls Logo

ABB REL650 - Page 369

ABB REL650
516 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
For a bus-section disconnector, these conditions from the B1 busbar section are valid:
en04000496_ansi.vsd
289OPTR (22089OTR)(bay 1/sect.B1)
S1DC_OP
VPS1_DC
EXDU_BB
289OPTR (22089OTR)(bay n/sect.B1)
. . .
. . .
. . .
VP289TR (V22089TR)(bay 1/sect.B1)
VP289TR (V22089TR)(bay n/sect.B1)
EXDU_BB (bay 1/sect.B1)
EXDU_BB (bay n/sect.B1)
. . .
. . .
. . .
. . .
. . .
. . .
AND
AND
AND
ANSI04000496 V1 EN
Figure 168: Signals from any bays in section B1 to a bus-section disconnector
For a bus-section disconnector, these conditions from the B2 busbar section are valid:
en04000497_ansi.vsd
289OPTR (22089OTR)(bay 1/sect.B2)
S2DC_OP
VPS2_DC
EXDU_BB
289OPTR (22089OTR)(bay n/sect.B2)
. . .
. . .
. . .
VP289TR(V22089TR) (bay 1/sect.B2)
VP289TR(V22089TR) (bay n/sect.B2)
VPDCTR (B2/B3)
EXDU_BB (bay n/sect.B2)
. . .
. . .
. . .
. . .
. . .
. . .
AND
DCOPTR (B2/B3)
EXDU_BB (bay 1/sect.B2)
EXDU_DC (B2/B3)
AND
AND
ANSI04000497 V1 EN
Figure 169: Signals from any bays in section B2 to a bus-section disconnector
1MRK 506 334-UUS A Section 11
Control
363
Application manual

Table of Contents

Other manuals for ABB REL650

Related product manuals