ABB Relion 670 series - Measuring the Operating Limit of Set Values

ABB Relion 670 series
330 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
X1
R
X
85%
1
3
5
2
6
4
50% RLdFwd
ArgNegRes
0.5·RFltFwdPP
LdAngle
ANSI09000735-1-en.vsd
ArgDir
60°
)/( phaseW
)/( phaseW
7
ANSI09000735 V1 EN-US
Figure 28: Operating characteristic for phase selection function, forward direction phase-to-phase
faults
Table 23: Test points for phase-to-phase loops A-B (Ohm/phase)
Test point
Reach Value Comments
1 X X1
R 0
2 X 0
R RLdFwd When RLdFWd < 0,5·RFLdFwPP
R 0.5·RFLdFwPP When RLdFwd > 0,5·RFLdFwPP
3 X 0.85·X1 R=0.491·X1+0.5 RFLdFwdPP
R 0.85·X1·1/tan(60°)+0.5
RFLdFwdPP
4 X 0.85·X1 Can be limited by RFLdFwPP
R -0.85·X1·tan (AngNegRes-90°)
5 X 0.5·RFLdFwdPP·tan (ArgLd) Only when RLdFwd < RFLdFwPP
R 0.5·RFLdFwdPP
6 X -0.5·RLdFwd·tan (ArgDir)
R 0.5·RLdFwd
Table 23 is used together with figure 28.
11.4.2.1 Measuring the operating limit of set values
M13906-73 v6
Procedure:
Section 11 1MRK 504 165-UUS Rev. J
Testing functionality by secondary injection
112 Transformer protection RET670
Commissioning manual