ABB Relion 670 series - Automatic Switch Onto Fault Logic ZCVPSOF; Function Revision History

ABB Relion 670 series
330 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IEC10000142-1-en.vsd
0
1
2
COMMON TRIP COMMAND (trip)
-1
0
1
TRIPZ1 (tripZone1)
0
1
2
TRIPZ2 (tripZone2)
0
1
2
START (start)
0
1
2
GENMODE (generatorMode)
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5
-1
0
1
time in seconds
MOTMODE (motorMode)
IEC10000142 V1 EN-US
Figure 44: Boolean output signals for the injected current with two components: a 50 Hz current
component and a 49.5 Hz current component
11.4.13 Automatic switch onto fault logic ZCVPSOF
M13850-2 v9
Prepare the IED for verification of settings outlined in Section "Preparing the IED to verify settings".
The automatic switch onto fault logic function ZCVPSOF is checked using secondary injection tests.
ZCVPSOF is activated either by the external input BC or by the internal DLD. FUFSPVC is done with a
pre-fault condition where the phase voltages and currents are at zero. A three-phase fault with zero
impedance and a three-phase fault with an impedance corresponding to the whole line is applied. This
fault shall cause an instantaneous trip and result in a TRIP indication.
11.4.13.1 Function revision history
GUID-A7F84AD6-F164-491B-B25E-D3BB002E1BDA v3
Document
revision
Product
revision
History
A 2.2.1 -
B 2.2.1 -
C 2.2.2 -
D 2.2.3 -
E 2.2.3 -
Table continues on next page
Section 11 1MRK 504 165-UUS Rev. J
Testing functionality by secondary injection
160 Transformer protection RET670
Commissioning manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved