The signal BLKV should appear with almost no time delay.
The signals BLKZ and 3PH should not appear on the IED.
Only the distance protection function can trip.
Undervoltage-dependent functions must not trip.
3. Disconnect the dc voltage from the 89b binary input terminal.
4. Connect the nominal dc voltage to the MCBOP binary input.
The BLKVand BLKZ signals should appear without any time delay.
All undervoltage-dependent functions must be blocked.
5. Disconnect the dc voltage from the MCBOP binary input terminal.
6. Disconnect one of the phase voltages and observe the logical output signals on the binary outputs
of the IED.
BLKV and BLKZ signals should appear simultaneously wether the BLKV and BLKZ reset depends
on the setting SealIn “on” or “off”. If “on” no reset, if “off” reset.
7. After more than 5 seconds disconnect the remaining two-phase voltages and all three currents.
There should be no change in the high status of the output signals BLKV and BLKZ.
The signal 3PH will appear.
8. Establish normal voltage and current operating conditions simultaneously and observe the
corresponding output signals.
They should change to logical 0 as follows:
Signal 3PH after about 25ms
Signal BLKV after about 50ms
Signal BLKZ after about 200ms
11.10.2.2 Measuring the trip value for the negative sequence function
M1405-46 v12
Measure the trip value for the negative sequence function, if included in the IED.
1. Simulate normal operating conditions with the three-phase currents in phase with their
corresponding phase voltages and with all of them equal to their rated values.
2. Slowly decrease the measured voltage in one phase until the BLKV signal appears.
3. Record the measured voltage and calculate the corresponding negative-sequence voltage
according to the equation (observe that the voltages in the equation are phasors):
2
2
3
A B C
V V a V a V× = + × + ×
EQUATION1818-ANSI V1 EN-US (Equation 118)
Where:
A B C
andV V V
EQUATION1820-ANSI V1 EN-US
are the measured phase voltages
2
3
3
1 0, 5
2
j
a e j
p
×
= × = - +
.
IECEQUATION00022 V2 EN-US
4. Compare the result with the set value of the negative-sequence operating voltage (consider that the
set value 3V2PU is in percentage of the base voltage VBase).
1MRK 504 165-UUS Rev. J Section 11
Testing functionality by secondary injection
Transformer protection RET670 235
Commissioning manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved