11.5.4.3 Four step non-directional ground fault protection
SEMOD53296-202 v5
1. Do as described in Section 11.5.4.2, but without applying any polarizing voltage.
11.5.4.4 Completing the test
SEMOD53296-122 v5
Continue to test another function or end the test by changing the TESTMODE setting to Disabled.
Restore connections and settings to the original values, if changed for testing purposes.
11.5.5 Four step negative sequence overcurrent protection NS4PTOC
(46I2)
GUID-EB1A8DFD-5BAC-4024-ADA2-D9BE7A2B50A0 v2
Prepare the IED for verification of settings as outlined in section "Preparing for test" in this chapter.
11.5.5.1 Function revision history
GUID-FEAFB742-D0DA-4F9E-B4AC-84E568301282 v2
Document
revision
Product
revision
History
A 2.2.1 -
B 2.2.1 -
C 2.2.2 -
D 2.2.3 -
E 2.2.3 -
F 2.2.4 -
G 2.2.4 Maximum value changed to 2000.0 % of IBase for IMin1, IMin2, IMin3 and IMin4 settings.
H 2.2.5 -
GUID-F7AA2194-4D1C-4475-8853-C7D064912614 v4
When inverse time overcurrent characteristic is selected, the trip time of the stage will be
the sum of the inverse time delay and the set definite time delay. Thus, if only the inverse
time delay is required, it is important to set the definite time delay for that stage to zero.
GUID-F973601F-BC67-4E4F-A4CA-BE6253E2FB92 v3
Procedure
1. Connect the test set for injection of three-phase currents and voltages to the appropriate CT and
VT inputs of the IED.
2. Inject pure negative sequence current, that is, phase currents with exactly same magnitude,
reversed sequence and exactly 120° phase displaced into the IED with an initial value below
negative sequence current pickup level. No output signals should be activated. Check under
NS4PTOC function Service Values that correct I2 magnitude is measured by the function.
3. Set the injected negative sequence polarizing voltage slightly larger than the set minimum
polarizing voltage (default 5 % of Vn) and set the injection current to lag the voltage by an angle
equal to the set reference characteristic angle (180° - AngleRCA) if the forward directional function
is selected.
If reverse directional function is selected, set the injection current to lag the polarizing voltage by an
angle equal to RCA.
Section 11 1MRK 504 165-UUS Rev. J
Testing functionality by secondary injection
172 Transformer protection RET670
Commissioning manual