11.18.1.2 Completing the test
M11369-39 v4
Continue to test another function or end the test by changing the TESTMODE setting to Disabled.
Restore connections and settings to the original values, if changed for testing purposes.
11.19 Exit test mode
SEMOD53244-3 v6
The following procedure is used to return to normal operation.
After exiting the IED test mode, make sure that the MU is returned to normal mode.
1. Navigate to the test mode folder.
2. Change the Enable setting to Disable. Press the 'E' key and the left arrow key.
3. Answer YES, press the 'E' key and exit the menus.
Section 11 1MRK 504 165-UUS Rev. J
Testing functionality by secondary injection
292 Transformer protection RET670
Commissioning manual