5. Activate BLOCK binary input and check that the outputs TEMPALM, TEMPLO, ALARM and
LOCKOUT disappear.
6. Reset the BLOCK binary input.
7. Ensure that temperature lockout condition exists and then activate the reset lockout input
RESETLO and check that the outputs TEMPLO and LOCKOUT reset.
11.14.1.4 Completing the test
GUID-DD08C598-A35C-4300-9555-A0877F7DC511 v3
Continue to test another function or end the test by changing the TestMode setting to Off. Restore
connections and settings to their original values, if they were changed for testing purposes.
11.14.2 Liquid medium supervision SSIML
GUID-6426FDDA-B949-4FE7-BF42-B52014A9344B v5
Prepare the IED for verification of settings as outlined in section "
"Preparing the IED to verify settings"" in
this chapter.
Values of logical signals for SSIML protection are available on the local HMI under Main menu /Test /
Function status /Monitoring /InsulationLiquid(71) /SSIML(71):x , where x = 1, 2,....4.
Check that the input logical signal BLOCK is logical zero and that on the local HMI, the logical signals
LVLALM, LVLLO, TEMPALM, TEMPLO, ALARM and LOCKOUT are logical zero.
11.14.2.1 Function revision history
GUID-751C8C78-891D-423B-825A-0774D0B6C658 v2
Document
revision
Product
revision
History
A 2.2.1 -
B 2.2.1 -
C 2.2.2 -
D 2.2.3 -
E 2.2.3 -
F 2.2.4 -
G 2.2.4 Binary quality inputs SENLVLQ and SENTEMPQ have been added for pressure and
temperature sensor signals in order to control alarm and lockout signals. Whenever there is
no sensor, the quality of the binary input will be low. If sensor quality is low, then lockout and
alarm signals will get reset.
H 2.2.5 -
11.14.2.2 Testing the liquid medium supervision for level alarm and level lockout
conditions
GUID-C1F1E6CA-9512-4358-A4E7-84CC3698D156 v4
1. Connect the binary inputs to consider liquid level to initiate the alarms.
2. Activate the binary input SENLEVELQ.
3. Consider the analogue level input SENLEVEL and set SENLEVEL to a value lower than
LevelAlmLimit or activate binary input signal SENLVLALM, check that outputs LVLALM and ALARM
are activated after a set time delay of tLevelAlarm.
4. Liquid level lockout input SENLVLLO can be used to set LVLLO.
1MRK 504 165-UUS Rev. J Section 11
Testing functionality by secondary injection
Transformer protection RET670 277
Commissioning manual