4. Compare the harmonic amplitude level value with the set warning limit value.
5. Continue to inject the same level of harmonics level until the TDDALM signal appears and note
down the time from TDDWRN set to TDDALM set.
6. Compare the noted time value with the set time limit value of alarm.
Verifying the warning and alarm time limit of individual harmonic distortions IHD,
WrnLimit#HD and tDelayAlm#HD (where # = 2
nd
, 3
rd
, 4
th
…9
th
)
GUID-C10AB22D-5FC7-47B4-B619-EAC46D1C2ECF v3
1. Supply the IED with current at rated value.
2.
Apply 2
nd
order harmonic along with injected current signal.
3. Slowly increase the harmonic amplitude until the 2NDHDWRN signal appears.
4. Compare the harmonic amplitude level value with the set warning limit value.
5. Continue to inject the same level of harmonics level until the 2NDHDALM signal appears and note
down the time from 2NDHDWRN signal set to 2NDHDALM signal set.
6. Compare the noted time value with the set time limit value of alarm.
7.
Repeat Steps
2 to 6 for the harmonics until 9
th
order.
11.14.9.2 Completing the test
GUID-EDB51B29-9556-4EF4-94E6-5DC6B8C0F13A v1
Continue to test another function or end the test by changing the TestMode setting to Off. Restore
connections and settings to their original values, if they were changed for testing purposes.
11.14.10 Function revision history
GUID-E828F930-88FF-4D5B-8304-2BD3B89919B8 v1
Document
revision
Product
revision
History
D 2.2.3 -
E 2.2.3 -
F 2.2.4 -
G 2.2.4 -
H 2.2.4 -
J 2.2.5
Updated monitoring till 9
th
order voltage harmonics. Refer to document revision H for
monitoring till 5
th
order voltage harmonics.
11.14.11 Voltage harmonic monitoring VHMMHAI(VTHD)
GUID-B2F24353-AAEA-4520-BB1C-5FD5FFCFC67B v1
GUID-804F309E-B02F-4F6B-B0FC-2C7AE3F12DBA v2
Prepare the IED for verification of settings outlined in Section
"Preparing the IED to verify settings".
11.14.11.1 Verifying the signals and settings
GUID-1A5BBF82-94AE-4E87-B951-CA007CC36CF1 v1
The voltage can be injected using common test equipment.
Verifying the warning and alarm time limit of THD, WrnLimitTHD and tDelayAlmTHD
GUID-3E56D8AC-9461-4EEA-83A8-522CA177563E v1
1. Supply the IED with voltage at rated value.
2. Apply harmonics at the numerical multiple of fundamental frequency along with the injected voltage
signal.
3. Slowly increase the harmonic amplitudes until the THDWRN signal appears.
Section 11 1MRK 504 165-UUS Rev. J
Testing functionality by secondary injection
284 Transformer protection RET670
Commissioning manual