ABB Relion 670 series - Test of the Boundary between Zone 1 and Zone 2, Which Is Defined by the Parameter Reachz1

ABB Relion 670 series
330 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
V V
V
V
V
ts t FwdZ
VT s
VT p
= × × = × × =0 9 0 9 11931
0 1
13 8
77 81. .
.
.
.
,
,
,
EQUATION14063 V1 EN-US (Equation 37)
=
=
=V
ForwardX
ForwardR
ts
arctan arctan
.
.
59 33
8 19
82..14°
EQUATION14058 V1 EN-US (Equation 38)
frequency of V
ts
= 50 Hz
I I
I
I
A
s
CTs
CTp
50 50
10459
1
9000
1 162= × = × = .
EQUATION14059 V1 EN-US (Equation 39)
I
50s
= 0º
frequency of I
50s
= 50 Hz
It I
I
I
A
fs
CTs
CTp
tf= × = × =10459
1
9000
1 162.
EQUATION14062 V1 EN-US (Equation 40)
I
tfs
= 180º
frequency of I
tfs
= 49.5 Hz
Expected result: start of the protection function and trip in zone 2, when trip conditions are fulfilled.
11.4.12.3 Test of the boundary between zone 1 and zone 2, which is defined by the
parameter ReachZ1
GUID-BE180E07-7D4B-4842-81FB-244DE8897430 v1
The trajectory of the impedance traverses the lens characteristic in zone 2
GUID-17F6AC8D-1F57-4245-A61D-776D469DD153 v1
Preliminary steady state test at 50 Hz
GUID-3D42E43D-873E-4271-9AAF-3B2789FF3B17 v1
Go to Main menu /Test /Function status /Impedance protection /OutOfStep(78,Ucos) /
OOSPPAM(78,Ucos):1 /Outputs to check the available service values of the function block
OOSPPAM.
Apply the following three-phase symmetrical quantities (the phase angle is related to phase L1):
V V
V
V
V
ts t RZ
VT s
VT p
= × × = × × =1 1 1 1 1435
0 1
13 8
11 44
1
. .
.
.
.
,
,
,
EQUATION14065 V1 EN-US (Equation 41)
=
=
=V
ForwardX
ForwardR
ts
arctan arctan
.
.
59 33
8 19
82..14°
EQUATION14058 V1 EN-US (Equation 42)
frequency of V
ts
= 50 Hz
I I
I
I
A
s
CTs
CTp
50 50
10459
1
9000
1 162= × = × = .
EQUATION14059 V1 EN-US
(Equation 43)
I
50s
= 0º
Section 11 1MRK 504 165-UUS Rev. J
Testing functionality by secondary injection
152 Transformer protection RET670
Commissioning manual