frequency of I
50s
= 50 Hz
It I
I
I
A
fs
CTs
CTp
tf= × = × =10459
1
9000
1 162.
EQUATION14062 V1 EN-US (Equation 44)
I
tfs
= 0º
frequency of I
tfs
= 50 Hz
Check that the service values (VOLTAGE, CURRENT, R(%), X(%)) are according to the injected
quantities and that ROTORANG is close to 3.14 rad. For this particular injection the service values
are:
VOLTAGE = 1.58 kV
CURRENT = 20918 A
R = 1.08%
X = 7.85%
ROTORANG = -3.04 rad
Note that these values identify a point inside the lens characteristic, in the Zone 2, that is close to the
boundary between zone 1 and zone 2. The START is issued, but no TRIP is performed.
Execution of the dynamic test
GUID-53964189-42E4-4C4B-BFCD-64888BA938EF v1
The test may be performed by using two states of a sequence tool that is a basic feature of test sets.
State 1: pre-test condition.
Steady voltage and current are applied in order to get a steady high impedance, that is a point in the
plane R-X that is far away from the lens characteristic. Define the following three-phase symmetrical
quantities (the phase angle is related to phase L1):
V V
V
V
V
ts t RZ
VT s
VT p
= × × = × × =1 1 1 1 1435
0 1
13 8
11 44
1
. .
.
.
.
,
,
,
EQUATION14065 V1 EN-US (Equation 45)
=
=
=V
ForwardX
ForwardR
ts
arctan arctan
.
.
59 33
8 19
82..14°
EQUATION14058 V1 EN-US (Equation 46)
frequency of V
t
= 50 Hz.
I
50s
= 0 A
I
tfs
= 0 A
State 2: main test step.
Define the following three-phase symmetrical quantities (the phase angle is related to phase L1):
V V
V
V
V
ts t RZ
VT s
VT p
= × × = × × =1 1 1 1 1435
0 1
13 8
11 44
1
. .
.
.
.
,
,
,
EQUATION14065 V1 EN-US (Equation 47)
=
=
=V
ForwardX
ForwardR
ts
arctan arctan
.
.
59 33
8 19
82..14°
EQUATION14058 V1 EN-US (Equation 48)
frequency of V
t
= 50 Hz
1MRK 504 165-UUS Rev. J Section 11
Testing functionality by secondary injection
Transformer protection RET670 153
Commissioning manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved