Figure 52: Connection of the test set to the IED for test of V2 block level
where:  
1 is three-phase voltage group1 (V1)
2 is three-phase voltage group2 (V2)
2. Apply voltage higher than the highest set value of VDTrip, V1Low and V2Low to the V1 three-phase
inputs and to one phase of the V2 inputs according to figure 
52.
The voltage differential PICKUP signal is set.
3. Decrease slowly the voltage in phase VC of the test set until the PICKUP signal resets.
4. Check V2 blocking level by comparing the voltage level at reset with the set undervoltage blocking
V2Low.
11.6.5.3  Check of voltage differential trip and alarm levels
SEMOD175258-104 v3
Procedure
1. Connect voltages to the IED according to valid connection diagram and figure 
53.
1MRK 504 165-UUS Rev. J Section 11
Testing functionality by secondary injection
Transformer protection RET670 211
Commissioning manual