EasyManua.ls Logo

ABB Relion 670 series - Check of Voltage Differential Trip and Alarm Levels

ABB Relion 670 series
330 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VA
VB
VC
VN
VA
VA
VB
VC
I
E
D
T
E
S
T
S
E
T
I
E
D
ANSI07000107-1-en.vsd
VB
VC
VN
1
2
ANSI07000107 V2 EN-US
Figure 52: Connection of the test set to the IED for test of V2 block level
where:
1 is three-phase voltage group1 (V1)
2 is three-phase voltage group2 (V2)
2. Apply voltage higher than the highest set value of VDTrip, V1Low and V2Low to the V1 three-phase
inputs and to one phase of the V2 inputs according to figure
52.
The voltage differential PICKUP signal is set.
3. Decrease slowly the voltage in phase VC of the test set until the PICKUP signal resets.
4. Check V2 blocking level by comparing the voltage level at reset with the set undervoltage blocking
V2Low.
11.6.5.3 Check of voltage differential trip and alarm levels
SEMOD175258-104 v3
Procedure
1. Connect voltages to the IED according to valid connection diagram and figure
53.
1MRK 504 165-UUS Rev. J Section 11
Testing functionality by secondary injection
Transformer protection RET670 211
Commissioning manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved

Table of Contents

Other manuals for ABB Relion 670 series

Related product manuals