The internal events are time tagged with a resolution of 1ms and stored in a list. The list can store up to
40 events. The list is based on the FIFO principle, when it is full, the oldest event is overwritten. The list
cannot be cleared and its content cannot be erased.
The internal events in this list not only refer to faults in the IED, but also to other activities, such as
change of settings, clearing of disturbance reports, and loss of external time synchronization.
The information can only be retrieved from the Parameter Setting software package. The PC can be
connected either to the port at the front or at the rear of the IED.
These events are logged as internal events.
Table 44: Events available for the internal event list in the IED
Event message: Description Generating signal:
INT--FAIL Off Internal fail status INT--FAIL (reset event)
INT--FAIL INT--FAIL (set event)
INT--WARNING Off Internal warning status lNT--WARNING (reset event)
INT--WARNING lNT--WARNING (set event)
IOn--Error Off In/Out module No. n status IOn--Error (reset event)
IOn--Error IOn--Error (set event)
ADMn-Error Off Analog/Digital module No. n
status
ADMn-Error (reset event)
ADMn-Error ADMn-Error (set event)
MIM1-Error Off mA-input module status MIM1-Error (reset event)
MIM1-Error MIM1-Error (set event)
INT--RTC Off Real Time Clock (RTC) status INT--RTC (reset event)
INT--RTC INT--RTC (set event)
INT--TSYNC Off External time synchronization
status
INT--TSYNC (reset event)
INT--TSYNC INT--TSYNC (set event)
INT--SETCHGD Any settings in IED changed
DRPC-CLEARED All disturbances in Disturbance
report cleared
The events in the internal event list are time tagged with a resolution of 1ms.
This means that, when using the PC for fault tracing, it provides information on the:
Module that should be changed.
Sequence of faults, if more than one unit is faulty.
Exact time when the fault occurred.
15.2.3 Diagnosing the IED status via the LHMI hint menu
GUID-7E8503E9-441B-487A-9CD7-B43463D1CAE5 v5
In order to help the user, there is an LHMI page labeled ‘Hints’. This page is located under Main menu /
Diagnostics/IED status /Hints. For each activated hint there is a headline. From the headline view, an
explanation page can be entered, giving the user more information and hints about the particular topic.
Section 15 1MRK 504 165-UUS Rev. J
Troubleshooting
308 Transformer protection RET670
Commissioning manual