For example, if there is a configuration to use IEC 61850 9–2 analog data, but no data arrives on the
access point, then the IED will use substituted data and most protection functions will be blocked. This
condition will be indicated with a sub-menu under Hints, where details about this condition are shown.
The Hint menu is a way to assist the user in troubleshooting.
The Hint menu is currently only available in English. All the entries are in English,
regardless of which language is selected.
The supported list of hints are as follows:
Table 46: Hint menu
Headline Explanation
Incorrect setting of SyncLostMode There are two explanations possible:
SyncLostMode is set to Block, no time source is configured
to achieve the required accuracy. Unless a high accuracy
time source is selected, the function dependent on high
time accuracy will be blocked.
SyncLostMode is set to BlockOnLostUTC, but there is no
UTC capable synch source (GPS, IRIG-B) used. Unless a
UTC capable time source is selected, the function
dependent on high time accuracy will be blocked.
Sampled value substituted <Access Point><Hardware Module Identifier><svID>
Where the Hardware Module Identifier is the same as given
in PCM600, e.g. AP1: MU1_9201 svID: <Hitachi Power
grids_MU0101>
Time diff: IED vs Sampled value <Access Point><Hardware Module Identifier><svID>
Where the Hardware Module Identifier is the same as given
in PCM600, e.g. AP1: MU1_9201 svID: <Hitachi Power
grids_MU0101>
Frequency diff: IED vs Sampled value <Access Point><Hardware Module Identifier><svID>
Where the Hardware Module Identifier is the same as given
in PCM600, e.g. AP1: MU1_9201 svID: <Hitachi Power
grids_MU0101>
Wrong cycle time for PMU report Wrong cycle time on SMAI or 3PHSUM block connected to
Phasor Report block. The SMAI or 3PHSUM block should
have same cycle time as that of Phasor Report.
PMU not connected to 3ph output The PMU phasor report input(s) must be connected to the
3ph output of SMAI or 3PHSUM.
Invalid value set for PMU Parameters There are two possible error conditions:
Check if the following parameters are set correctly on
PMUREPORT:1 ReportRate or SvcClass or parameter
PRIMVAL:1.FrequencySel is not set as 50Hz / 60Hz.
Check if the following parameters are set correctly on
PMUREPORT:1 ReportRate or SvcClass or RptTimetag or
parameter PRIMVAL:1.FrequencySel is not set as 50Hz /
60Hz.
Invalid phase angle reference The selected PhaseAngleRef corresponds to an analog
channel that is not configured. Configure a valid reference
channel.
Table continues on next page
1MRK 504 165-UUS Rev. J Section 15
Troubleshooting
Transformer protection RET670 309
Commissioning manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved