Headline Explanation
GOOSE is configured on a disabled port At least one of the access points configured for GOOSE is
disabled. The port can be disabled either through changing
the access point operation to off or by unchecking the
GOOSE protocol from the access point in the Ethernet
configuration in PCM600 or LHMI.
Enable GOOSE on access points:
<Access Points>, can be any of these: AP_FRONT, AP_1,
AP_2, AP_3, AP_4, AP_5, AP_6,AP_7, AP_8
LDCM not running the application image LDCM in <slot number> is running the factory image
instead of the application image. The factory image is older
than the required FW version and does not contain the
latest updates and fixes.
Reboot the IED. If the problem persists, update the LDCM
firmware or replace the board.
LDCM rate (2M) is not supported The <firmware version> does not support 2M mode. Set
the LDCM to 64k bit mode.
LDCM version is not accepted <device name> firmware version <version string> is not
accepted. The minimum accepted version is <version
string>.
Update the LDCM firmware or replace the board.
OEM not running the application image OEM in pos <slot number> is running the factory image
instead of the application image. The factory image is older
than the required FW version and does not contain the
latest updates and fixes.
Reboot the IED. If the problem persists, update the OEM
firmware or replace the board.
SFP unplugged from the slot SFP has been unplugged from the slot.
Check the connection.
Corresponding hardware(s) is set to fail.
SFP replaced with other type Configured and the detected SFP(s) are different.
Corresponding hardware(s) is set to fail.
Restart IED and consider reconfigure of HW modules in
LHMI path: \Main menu\Configuration\Reconfigure HW
modules to get the updated hardware list.
Non Hitachi Power grids vendor SFP detected Non Hitachi Power grids vendor SFP detected.
Corresponding hardware(s) is set to fail. Use Hitachi Power
grids approved SFP’s.
Merging unit has no access point Merging unit has no access point.
Check AP configuration.
FPGA version is not accepted FPGA version is not accepted.
If OEM or NUM FPGA code is of too low version, then
update.
Duplicate IP address detected Duplicate IP address detected.
Duplicate IP: <xxxx>
Access Point: <xxxx>
Access Point MAC: <xxxx>
IP duplicator's MAC: <xxxx>
Table continues on next page
Section 15 1MRK 504 165-UUS Rev. J
Troubleshooting
310 Transformer protection RET670
Commissioning manual