EasyManua.ls Logo

ABB Relion 670 series - Verifying the Back-Up Trip Mode

ABB Relion 670 series
330 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1. Set RetripMode = Off.
2. Apply the fault condition, including initiation of CCRBRF (50BF), well above the set current value.
3. Verify that no re-trip, but back-up trip is achieved after set time.
4. Disconnect AC and BFI_3P input signals.
Checking the re-trip with current check, RetripMode = UseFunctionMode
M12104-48 v8
1. Set RetripMode = UseFunctionMode.
2. Apply the fault condition, including initiation of CCRBRF (50BF), well above the set current value.
3. Verify that re-trip is achieved after set time t1 and back-up trip after time t2.
4. Apply the fault condition, including initiation of CCRBRF (50BF), with current below set current
value.
5. Verify that no re-trip, and no back-up trip is obtained.
6. Disconnect AC and BFI_3P input signals.
Checking re-trip without current check
M12104-58 v10
1. Set RetripMode = Always.
2. Apply the fault condition, including initiation of CCRBRF (50BF), well above the set current value.
3. Verify that re-trip is achieved after the set time t1, and the back-up trip after time t2.
4. Apply the fault condition, including initiation of CCRBRF (50BF), with current below set current
value.
5. Verify that re-trip is achieved after set time t1, but no back-up trip is obtained.
6. Disconnect AC and BFI_3P input signals.
11.5.9.6 Verifying the back-up trip mode
M12104-146 v5
In the cases below it is assumed that FunctionMode = Current is selected.
Checking that back-up tripping is not achieved at normal CB tripping
M12104-150 v8
Use the actual tripping modes. The case below applies to re-trip with current check.
1. Apply the fault condition, including initiation of CCRBRF (50BF), with phase current well above set
value Pickup_PH.
2. Interrupt the current, with a margin before back-up trip time, t2. It may be made at issue of re-trip
command.
3. Check that re-trip is achieved, if selected, but no back-up trip is obtained.
4. Disconnect AC and BFI_3P input signals.
The normal mode BuTripMode = 1 out of 3 should have been verified in the tests above. In applicable
cases the modes 1 out of 4 and 2 out of 4 can be checked. Choose the mode below, which corresponds
to the actual case.
Checking the case BuTripMode = 1 out of 4
M12104-165 v6
It is assumed that the ground-fault current setting Pickup_N is below phase current setting Pickup_PH.
1. Set BuTripMode = 1 out of 4.
2. Apply the fault condition, including initiation of CCRBRF (50BF), with one-phase current below set
Pickup_PH but above Pickup_N . The residual ground-fault should then be above set Pickup_N.
3. Verify that back-up trip is achieved after set time. If selected, re-trip should also appear.
4. Disconnect AC and BFI_3P input signals.
Section 11 1MRK 504 165-UUS Rev. J
Testing functionality by secondary injection
182 Transformer protection RET670
Commissioning manual