The figures illustrating the characteristic for the distance protection function can be used
when the load encroachment affects the zone characteristic and when it is not. The solid
lines designate the diagram applicable when the load encroachment is overlapping with
the zone. All the test points except 13 are valid for this case. When the load
encroachment does not overlap with the zone, the dotted lines and test point 13 are
valid. Test points 5, 6, and 7 are not valid for this measurement however.
X1set
R
X
(Ω/phase)
50%
80%
1
2
3
4
5
6
7
8
9
10
11
50% of RFPPZx/2
25% of RFPPZx/2
RFPP/2
12
ANSI05000368-2-en.vsdx
13
ArgDir
ArgLd
ANSI05000368 V2 EN-US
Figure 35: Distance protection characteristic with test points for phase-to-phase measurements
Table 30: Test points for phase-to-phase loops A-B (Ohm/phase)
Test point
Reach Set value Comments
1 X X1
set
R 0
2 X X1
set
R R1
set
3 X 0.8 x X1
set
R 0.8 x R1
set
+ RFPP/2
4 X 0.5 x X1
set
R 0.5 x R1
set
+ RFPP/2
5 X 0.85 x RFPP/2 x tan (LdAngle) If RLdFwd < 0.85 x RFPP/2
R 0.85 x RFPP/2
6 X RLdFwd x tan (LdAngle) If RLdFwd < RFPP/2
R RLdFwd
7 X 0 If RLdFwd < RFPP/2
R RLdFw
Table continues on next page
Section 11 1MRK 504 165-UUS Rev. J
Testing functionality by secondary injection
124 Transformer protection RET670
Commissioning manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved